Heat Shrinkable Terminations Suitable 36 KV For 1 Core XLPE/EPR Insulated Cable

Daffodil Heat Shrinkable Cable Terminations 36 kV for XLPE/EPR Insulating Cable are suitable for XLPE or EPR insulation up to 36 kV..

  • Fully designed & tested in accordance to IS & IEC standards
  • Wide range and possible to tailor for any cable type
  • Excellent performance & reliability
  • Suitable for use with mechanical ferrules (available on request)
  • Field proven technology
ORDERING REFERENCE
CABLE SIZE (Sq. mm) For 11 kV Indoor Terminations (Kit Code)
1 x 16 - 50 DXES - 11
1 x 70 - 120 DXES - 12
1 x 150 - 300 DXES - 13
1 x 400 - 630 DXES - 14
1 x 800 - 1000 DXES - 15
CABLE SIZE (Sq. mm) For 11 kV Outdoor Terminations (Kit Code)
1 x 16 - 50 DXOS - 11
1 x 70 - 120 DXOS - 12
1 x 150 - 300 DXOS - 13
1 x 400 - 630 DXOS - 14
1 x 800 - 1000 DXOS - 15
CABLE SIZE (Sq. mm) For 22 kV Indoor Terminations (Kit Code)
1 x 16 - 50 DXES - 21
1 x 70 - 150 DXES - 22
1 x 185 - 300 DXES - 23
1 x 400 - 630 DXES - 24
1 x 800 - 1000 DXES - 25
CABLE SIZE (Sq. mm) For 22 kV Outdoor Terminations (Kit Code)
1 x 16 - 50 DXOS - 21
1 x 70 - 150 DXOS - 22
1 x 185 - 300 DXOS - 23
1 x 400 - 630 DXOS - 24
1 x 800 - 1000 DXOS - 25
CABLE SIZE (Sq. mm) For 33 kV Indoor Terminations (Kit Code)
1 x 25 - 50 DXES - 31
1 x 70 - 185 DXES - 32
1 x 240 - 400 DXES - 33
1 x 500 - 800 DXES - 34
1 x 1000 DXES - 35
CABLE SIZE (Sq. mm) For 33 kV Outdoor Terminations (Kit Code)
1 x 25 - 50 DXOS - 31
1 x 70 - 185 DXOS - 32
1 x 240 - 400 DXOS - 33
1 x 500 - 800 DXOS - 34
1 x 1000 DXOS - 35
Technical Specifications
Test Sequence 6.35/11 kV 12.7/22 kV 19/33 kV
A.C. withstand test 29kV, 5min, no flashover 58kV, 5min, no flashover 86kV, 5min, no flashover
Partial discharge test 11kV < 10pc (Max.) 22kV < 10pc (Max.) 33kV < 10pc (Max.)
Thermal Cycles (63 cycles) under 95-100°C 16kV under 95-100°C 32kV under 95-100°C 48kV
Impulse voltage test 75kV no flashover 125kV no flashover 170kV no flashover
A.C. withstand test 16kV, 15 min, no flashover 32kV, 15 min, no flashover 48kV, 15 min, no flashover
Humidity test (Indoor) No flashover, tracking erosion or mechanical damage occurred at 300hrs, 8kV No flashover, tracking erosion or mechanical damage occurred at 300hrs, 16kV No flashover, tracking erosion or mechanical damage occurred at 300hrs, 24kV
Salt Fog test (Outdoor) No flashover, tracking erosion or mechanical damage occurred at 1000hrs, 8kV No flashover, tracking erosion or mechanical damage occurred at 1000hrs, 16kV No flashover, tracking erosion or mechanical damage occurred at 1000hrs, 24kV