Daffodil Heat Shrinkable Straight Joints Upto 36 kV for XLPE/EPR Insulating Cable are suitable for Cable jointing Kit low voltage fixed or flexible cables having XLPE or EPR insulation up to 36kV.
CABLE SIZE (Sq. mm) | FOR 11 kV (Kit Code) |
---|---|
3 x 16 - 50 | DXS - 11 |
3 x 70 - 95 | DXS - 12 |
3 x 120 - 185 | DXS - 13 |
3 x 240 - 300 | DXS - 14 |
3 x 400 - 500 | DXS - 15 |
CABLE SIZE (Sq. mm) | FOR 22 kV (Kit Code) |
3 x 25 - 50 | DXS - 21 |
3 x 70 - 95 | DXS - 22 |
3 x 120 - 150 | DXS - 23 |
3 x 185 - 240 | DXS - 24 |
3 x 300 - 400 | DXS - 25 |
CABLE SIZE (Sq. mm) | FOR 33 kV (Kit Code) |
3 x 35 - 70 | DXS - 31 |
3 x 95 - 150 | DXS - 32 |
3 x 185 - 300 | DXS - 33 |
3 x 400 | DXS - 34 |
Test Sequence | Requirements for 15kV | Requirements for 24kV | Requirements for 36kV |
---|---|---|---|
D.C. Voltage with stand / 15 min | 48 kV | 96 kV | 144 kV |
A.C. Voltage with stand / 1 min | 35 kV | 50 kV | 75 kV |
Impulse Voltage with stand | 75 kV | 125 kV | 170 kV |
Discharge Extinction Voltage(<5pc)< /td> | More than 13kV | More than 25.4kV | More than 38kV |